Description
DIN96 energy meters for measuring kWh of individual machines or complete systems. Manufactured to BS5685, IEC521 with a class accuracy of 1% to IEC1036, and supplied in a 96 x 96 mm DIN case. The kilowatt hour meter has a 7 digit non resettable mechanical counter. Pulsed output is available to send to PLC’s data loggers and computers. Analogue mA output is also available.
Application
For monitoring the consumption of electricity in a single or 3 phase system. Savings can made by monitoring and using electricity at the optimum time.
Technical Specification
Rated Current | 1 or 5A (<0.2VA / phase purden) |
Range 10-120% of rated current | |
Overload 4 x rated current continuous | |
50 x rated current for 1 second | |
Rated Voltage | 57-500V (< 0.2VA / phase burden) |
Range 80-120% of rated voltage | |
Overload 1.5 x rated voltage continuous | |
4 x rated voltage for 1 second | |
Frequency | 50 or 60Hz nominal range |
Auxiliary | 115 / 230 / 400 AC Voltage |
Pulsed Output | Normally open volt free contact, |
50V 150mA 5W AC / DC | |
Pulse rate: 0.1, 1 or 10 per kWh. | |
Pulse duration: 250msec standard | |
Analogue output | Rated value 0-1mA into < 5k Ohms |
0-20mA into % < 250k Ohms | |
Accuracy | Class 1 to IEC 1036 |
Operating Temp | -25ºC to +70ºC |
Temp Coefficient | 0.01% per 1ºC |
Material | Polycarbonate to UL94VO |
Enclosure | IP54 |
Mounting | 4 side brackets and screws |
Range
Description | Product Codes |
Single Phase | D96kWh1/M600-WM1 |
3 phase 3W balanced load | D96kWh2/M600-WM2 |
3 phase 4W balanced load | D96kWh3/M600-WM3 |
3 phase 3W unbalanced load | D96kWh4/M600-WM4 |
3 phase 4W unbalanced load | D96kWh9/M600-WM9 |
Ordering Information
- Product Code
- Current Transformer Ratio
- Voltage Transformer Ratio
- Frequency
- Auxiliary Voltage
Options
- Pulsed Output (0.1, 1 or 10 per kWh)
- Analogue Output
- Non standard pulse width
- Calibrate at temp other than 23ºC
- Calibration at Hz 35-450
Call us now on: +44 1922 640003